UX100-011A Data Logger HOBO Thermo-hygrometer for Temp/RH 2.5% with internal sensor View larger

UX100-011A Data Logger HOBO Thermo-hygrometer for Temp/RH 2.5% with internal sensor

Onset

New

Thermo-hygrometer Data Logger Energy/HVAC Indoor Applications for Air Quality.

165,00 €

Add to wishlist

Number of Channels 2: Temp + Rel. Humidity
ADC Bits 12 bit
Precision ±0.21°C
Resolution 0.024°C
With Display Yes
IP Classification Indoor IP50
Communications USB
Battery Life 1 year
Memory Capacity 84,650 measurements

The HOBO UX100-011 Thermo-hygrometer Temp/RH data logger records temperature and relative humidity (within 2.5% accuracy) in indoor environments with its integrated sensors. This logger is ideal for monitoring occupant comfort in office buildings, tracking food storage conditions in warehouses, logging temperature trends in server rooms, and measuring humidity levels in museums.

  • Easy-to view LCD display
  • Large memory capacity
  • Visual high & low alarm thresholds
  • New Burst and Statistics logging modes
  • User-replaceable RH sensor

Environment:
The UX100-011 Data Logger is for use in Indoor environments

Medidas:
The UX100-011 Data Logger supports the following measurements: Temperatura y Humedad Relativa

Sensor Temperatura:


Range: -20° to 70°C (-4° to 158°F) 

Accuracy: ±0.21°C from 0° to 50°C (±0.38°F from 32° to 122°F), see Plot A

Resolution: 0.024°C at 25°C (0.04°F at 77°F); see Plot A

Response Time: 4 minutes in air moving 1 m/s (2.2 mph)

Drift: <0.1°C (0.18°F) per year

Sensor RH:

Rango: 1% to 95%

Accuracy: ±2.5% from 10% to 90% typical to a maximum of ±3.5% including hysteresis, see Plot B

Resolution: 0.05% at 25°C (77°F)

Response Time: 11 seconds to 90% in airflow of 1 m/s (2.2 mph)

Drift: <1% per year typical

Registrador:


Logger Operating Range
Logging: -20° to 70°C (-4° to 158°F); 0 to 95% RH (non-condensing)
Launch/Readout: 0° to 50°C (32° to 122°F) per USB specification

Logging Rate: 1 second to 18 hours, 12 minutes, 15 seconds

Logging Modes: Normal, Burst or Statistics

Memory Modes: Wrap when Full or Stop when Full

Start Modes: Immediately, Push Button, Date & Time or Next Interval

Stop Modes: When Memory Full, Push Button, or Date & Time

Restart Mode: Push Button

Time Accuracy: ±1 minute per month at 25°C (77°F), see Plot C

Battery Life: 1 year, typical with logging rate of 1 minute and sampling interval of 15 seconds or greater

Battery Type: One 3V CR2032 lithium battery

Memory: 128 KB (84,650 measurements, maximum)

Download Type: USB 2.0 interface

Full Memory Download Time: 20 seconds

LCD: LCD is visible from: 0° to 50°C (32° to 122°F); the LCD may react slowly or go blank in temperatures outside this range

Dimensiones: 3.66 x 8.48 x 2.29 cm (1.44 x 3.34 x 0.9 in.)

Peso: 30 g (1.06 oz)

Environmental Rating: IP50

- The CE Marking identifies this product as complying with all relevant directives in the European Union (EU)