H723 VERIS AC Transducer (0-10VDC output) View larger

H723 VERIS AC Transducer (0-10VDC output)

Veris

New

Flyer:H723/H923 Manual:H723/H923

Veris AC Current Transducers (0-10VDC output).
H973 open coil & H723 closed coil, bothwith slide-switch selection for 3 different Amp Ranges.

Minimum Order: 3 Units

Volume discounts

Quantity Price
You Save
%
1+ 175,00 € 0%
2+ 168,00 € 4%
3+ 164,50 € 6%
4+ 157,50 € 10%
5+ 154,00 € 12%
6+ 148,75 € 15%

Add to wishlist

The Hawkeye models H723LC & H723HC provide accurate load trending information with a proportional 0-10VDC output signal.
There are three models available and each device offers three amperage range options, with slide-switch selection for easy field adjustment – no need for jumpers:
H723LC: 0 - 10/20/40A
H723HC: 0 - 50/100/200A

Applications:

  • Load trending
  • Motor control
  • Fan/pump status

Self-powered analog current sensor, 0-10VDC output

  • Self-gripping split-core for fast retrofit installation...no need to remove conductor
  • No jumpers on unit...reduces installation error
  • No external power required for sensor

Factory calibrated for ease of installation

  • Factory calibrated field-selectable ranges for high resolution and installation ease
  • One device to stock and install...reduces installation charges
  • Bracket can be installed in three different configurations...added flexibility
  • 100% solid state, no moving parts to fail
  • 5-year limited warranty
  • CE
Note: The price of all the models is the same.

Specifications:

  • Sensor Power Induced from monitored current
  • Insulation Class 300VAC RMS
  • Frequency Range 50/60Hz
  • Temperature Range -15° to 60°C (5° to 140°F)
  • Humidity Range 10 - 90% RH, non-condensing
  • Accuracy ±2% full scale from 10% to 100% (selected range)
  • Response Time 2 sec.
  • Terminal Block Maximum Wire Size 14 AWG
  • Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
  • Agency Approvals CE: EN61010-1:2001-2, CAT III, deg. 2, basic insulation